Refrigerant reference

Useful notes without pressure shortcuts

Use these notes for context, not as fixed charging targets. Pressure depends on saturation temperature, load, airflow or water flow, and the equipment.

25 of 25 refrigerants

Choose one to view properties and service guidance.

Charge by the procedure for the equipment in front of you. Use current pressure-temperature data and measured superheat/subcooling where the method calls for them. Do not use a pressure by itself as the charge test.

GWP values shown use the U.S. EPA Technology Transitions reference table. Regulatory values and assessment bases can differ by rule or source.

Diagnostic patterns

Read the whole refrigeration pattern

These combinations are clues, not diagnoses. Verify airflow or water flow, load, sensor accuracy, and the OEM charging method before changing the refrigerant charge.

Possible undercharge

High superheat + low subcooling after airflow/load are verified

Check first

Airflow, evaporator load, metering-device operation, and measurement accuracy

This pattern can support low refrigerant mass, but it should lead to a leak search and the OEM charging procedure. Do not top off by pressure alone.

Possible feed restriction

High superheat + normal/high subcooling

Check first

Filter-drier temperature drop, TXV/EEV command, sensing inputs, liquid-line condition, and charge history

Liquid can be backed up in the condenser/receiver while the evaporator is starved. Prove the restriction or metering-control fault before replacing a valve.

Possible overcharge / poor heat rejection

High condensing temperature/pressure with elevated subcooling

Check first

Condenser airflow or water flow, fan/pump staging, coil condition, ambient/entering-water temperature, and noncondensables

High head pressure is not automatically overcharge. Restore heat rejection and verify the complete operating pattern before recovering refrigerant.

Low superheat / floodback risk

Low superheat or evidence of liquid returning to the compressor

Check first

Airflow/load, EEV/TXV control, sensing bulb/thermistors, overfeeding, defrost/reheat sequence, and accumulator condition

Protect the compressor first. Determine why the evaporator is not fully boiling the refrigerant before extended operation.